Baseline study v0 (November 2026)

A first look at how often tank releases happen and what goes with them, using EPA national data, EPA UST Finder, Texas tank records and National Response Center reports.

  • Each year still adds more than 4,000 confirmed releases nationally (4,295 in FY2025); the cleanup backlog fell from 61,753 (FY2021) to 53,557 (FY2025).
  • 31.9% of open tanks with a known install date predate the 1988 federal technical rules.
  • In Texas, the 3-year release rate rises from 1.1% for facilities with tanks under 10 years old to 4.5% at 30–39 years. All-single-walled sites: 3.5%; all-double-walled: 1.8%.
  • Equipment failure (26%) and operator error (19%) are the leading reported causes of storage-tank incidents; 35% have no cause given.

Charts: UST Risk Explorer. Gaps: tank-level release causes are not in Texas public files; inspection and violation data (EPA ECHO) and DOT hazmat incidents (PHMSA) are not yet integrated.

First-generation release-risk model (v0.1.0)

Question. Which registered tank facilities are most likely to report a confirmed release in the next 3 years, using only what was knowable beforehand?

Data. Texas TCEQ tank registry and leaking-tank cases. Training: facilities as of January 1 of 2010, 2013, 2016 and 2019. Test: facilities as of January 1, 2022, scored against releases reported from 2022 through 2024. The test period was never used for training or tuning.

0.705

ROC AUC (95% CI 0.681–0.727)

28.5%

of releases in the top-scored 10% (CI 24.5%–32.6%)

456 / 19,550

test facilities with a release (2.3%)

Decision metric. Inspecting the 10% of facilities with the highest score would have covered 28.5% of the facilities that went on to report a release, versus 10% for a random 10% and 16.4% for “oldest tanks first”.

Share of 2022–2024 releases found when inspecting the top X% of facilities by score

Top 1%3.3%random: 1%
Top 5%14.9%random: 5%
Top 10%28.5%random: 10%
Top 20%46.1%random: 20%
Top 30%59.2%random: 30%
Top 50%78.7%random: 50%
ModelROC AUCPR AUCTop 10% captures
Logistic regression (v0, shipped)0.7050.05128.5%
Gradient-boosted trees0.6950.04924.8%
Logistic + location exposure (experiment)0.7080.05127.9%
Oldest tank age only0.6570.03616.4%
Random0.5000.02310.0%

Main drivers (higher risk): pressurized piping, older tanks, more and larger tanks, tanks installed before 1989, suction piping, single-walled tanks, retail sites. Lower risk: emergency-generator sites, and facilities with a prior or open release case (remediation and replacement often follow a release). These are associations, not causes.

Where it fails. 21% of test releases were at facilities scored in the bottom half, mostly newer, double-walled sites, where construction records say little. Operational data from pilots is needed there. 20% of test-period releases occurred at sites with no regulated tank in the ground at the start of 2022, which v0 cannot score. Calibration: v0 over-predicts slightly in the test period; use it to rank, not as exact probabilities.

A result we rejected. An earlier version scored AUC 0.80. We traced the gain to a data artifact: Texas clears a tank’s recorded substance when the tank is removed, so “no fuel recorded” quietly signaled a future removal, when releases are often found. Those fields were removed. We report the lower, honest number.

Multi-state model v0 (10 states, EPA UST Finder)

A second model applies the same design to Alabama, Arizona, Arkansas, Louisiana and New Jersey, plus Kansas, Maryland, Montana, North Carolina and Ohio with caveats, using EPA’s national UST Finder records. Tested on 2015–2017: ROC AUC 0.684; the top 10% of facilities held 22.5% of releases (oldest-tank-first: 14.1%). Scored on Texas without ever seeing Texas data: AUC 0.633. The other 40 states lack one or more required fields in the public composite; the state coverage page lists each reason and the next step.

National Risk & Efficiency Index — v0 methodology, prototype

0-100; higher = higher risk and/or less efficient release response, relative to other states. Three equally weighted pillars, each the average of its components’ percentile ranks across the 49 states (incl. DC) with complete data (excluded for missing inputs: SC, VT):

PillarComponent
LikelihoodConfirmed releases per 1,000 active USTs (FY21-25 avg)
LikelihoodShare of open tanks installed before 1989
LikelihoodShare of inspected facilities not in full technical compliance (FY25)
ExposureShare of tank facilities with private wells within 1,500 ft
ExposureShare of tank facilities in source-water protection areas
EfficiencyBacklog as share of all confirmed releases (FY25)
EfficiencyReleases confirmed per cleanup completed (FY21-25)

Sensitivity. Doubling the weight of any one pillar keeps rankings close to the base case (Spearman correlation 0.92–0.96; median rank change 2–4 places). Switching to min-max normalization gives 0.90. Individual states can move by up to 21 places, so single ranks should not be over-read.

Highest v0 scores (higher = higher risk and/or slower cleanup, relative to other states): OH (72.7), OK (71), NH (69.4), OR (68.8), MI (68.5), IN (67.7), NM (66.2), IL (64.6), WV (64.5), TN (62.1).

Not yet included: modeled facility-level risk (only Texas has a model), inspection coverage, and cleanup cost. Data vintages differ across components. States report EPA measures differently. This is a starting point for discussion with state programs, not a ranking of state performance.

Publications

  • Ananya Sudhir. “Environmental Infrastructure Resilience for the U.S. Logistics Sector: A Climate and Economic Imperative.” SSRN working paper 5765243. SSRN
  • SiteClear methodology note v0 (draft, November 2026): HTML · PDF

Data sources

SourceUsed forDownloaded
EPA Semiannual Report of UST Performance Measures (FY2021–FY2025)State releases, cleanups, backlog, technical compliance2026-11-22
EPA UST Finder (national UST facilities, tanks, releases)Tank age and wall type, location exposure, release records2026-11-22 (2018–2021 data)
Texas TCEQ Petroleum Storage Tank registryTank-level construction, install and removal dates2026-11-22 (extract of 2026-09-02)
Texas TCEQ Leaking Petroleum Storage Tank sites (data.texas.gov)Release labels and history2026-11-22
National Response Center incident reports (CY2022–CY2025)Reported incident causes2026-11-22

All sources are public U.S. federal or state government records. No employer or other non-public data is used.

Model and method changelog

DateChange
2026-11-22Multi-state model v0.1.0 (10 states, EPA UST Finder) and 50-state data coverage audit. Montana wall type disabled after a leakage check.
2026-11-22Release-risk model v0.1.0 (Texas). Substance fields removed after a leakage check; test AUC 0.705.
2026-11-22National Risk & Efficiency Index v0 methodology and sensitivity analysis.
2026-11-22Baseline study v0: EPA, UST Finder, TCEQ and NRC data.